首页 | 本学科首页   官方微博 | 高级检索  
     

基于CPS标准的自动发电控制的探讨
引用本文:李作丽. 基于CPS标准的自动发电控制的探讨[J]. 英才高职论坛, 2007, 0(1)
作者姓名:李作丽
作者单位:山东英才职业技术学院机械制造及自动化工程学院 山东济南250104
摘    要:本文主要探讨了AGC中A1/A2标准的数学模型和针对A1/A2标准的AGC控制策略,详细介绍了一种基于CPS特点的理想AGC控制策略。在频率偏差大时,AGC的控制目标是尽量使ACE和频率偏差符号相反;在频率偏差较小时,AGC的控制目标是使ACE的绝对值最小。本文同时提出了对不同控制策略进行验证的方法,对AGC的实际应用具有重要的指导价值。

关 键 词:控制性能标准  互连电网  自动发电控制  区域控制误差

The Discussion of AGC Based on CPS Standard
LI Zuoli. The Discussion of AGC Based on CPS Standard[J]. The Forum of Yingcai Higher Vocational Education, 2007, 0(1)
Authors:LI Zuoli
Abstract:The A1/A2 standard mathematical model of AGC and AGC control strategy aimed at A1/A2 control standards are mainly discussed in the paper.A kind of ideal AGC control strategy based on CPS characteristic is also introduced in detail.When frequency departure is big,the goal of AGC control is to make ACE and the frequency departure symbol opposite as far as possible;when the frequency departure is small,the goal is to make ACE get the least absolute value.Simultaneously,the confirmation method of the different control strategy is proposed.This paper has the important instruction value to the AGC practical application.
Keywords:control performance standard(CPS)  power network  automatic electricity generation control(AGC)  area control error(ACE)